30 CFR §75.1101-7
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
- (a)The fire-control components of each water sprinkler system shall be installed, as far as practicable in accordance with the recommendations set forth in National Fire Protection Association 1968-69 edition, Code No. 13, “Installation of Sprinkler Systems” and such systems' components shall be of a type approved by the Underwriters' Laboratories, Inc., Factory Mutual Research Corp.
- (b)Each sprinkler system shall provide protection for the motor drive belt takeup, electrical controls, gear reducing unit, and the 50 feet of fire-resistant belt, or 150 feet of nonfire-resistant belt adjacent to the belt drive.
- (c)The components of each water sprinkler system shall be located so as to minimize the possibility of damage by roof fall or by the moving belt and its load.