30 CFR §75.827
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
- (a)Guarding.
- (b)Suspended cables and cable crossovers. When equipment must cross any portion of the cable, the cable must be either:
- (1)Suspended from the mine roof; or
- (2)Protected by a cable crossover having the following specifications:
- (i)A minimum length of 33 inches;
- (ii)A minimum width of 17 inches;
- (iii)A minimum height of 3 inches;
- (iv)A minimum cable placement area of two and one half-inches (2 1/2″) high by four and one-quarter inches (4 1/4″) wide;
- (v)Made of nonconductive material;
- (vi)Made of material with a distinctive color. The color black must not be used; and
- (vii)Made of material that has a minimum compressive strength of 6,400 pounds per square inch (psi).