StacksVerified U.S. regulatory reference

30 CFR Part 18, Appendix I

Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov
Table No.Title
1Portable power cable ampacities—600 volts.
2Portable cord ampacities—600 volts.
3Portable power cable ampacities—601 to 5,000 volts.
4Normal diameter of round cables with tolerances in inches—600 volts.
5Nominal dimension of flat cables with tolerances in inches—600 volts.
6Nominal diameter of heavy jacketed cords with tolerances in inches—600 volts.
7Nominal diameter of three-conductor portable power cables with tolerances in inches—601 to 5,000 volts.
8Fuse ratings or instantaneous settings of circuit breakers for short-circuit protection of portable cables.
9Specifications for portable cables longer than 500 feet.
10High voltage trailing cable ampacities and outside diameters.
Conductor size—AWG or MCMSingle conductor | 2-conductor, round or flat | 3-conductor, round or flat | 4-conductor | 5-conductor | 6-conductor
845 | 40 | 35 | 30 | 25 | 20
660 | 50 | 50 | 40 | 35 | 30
485 | 70 | 65 | 55 | 45 | 35
395 | 80 | 75 | 65 | 55 | 45
2110 | 95 | 90 | 75 | 65 | 55
1130 | 110 | 100 | 85 | 75 | 65
1/0150 | 130 | 120 | 100 | 90 | 80
2/0175 | 150 | 135 | 115 | 105 | 95
3/0205 | 175 | 155 | 130 | 120 | 110
4/0235 | 200 | 180 | 150 | 140 | 130
250275 | 220 | 200 | 160 | |
300305 | 240 | 220 | 175 | |
350345 | 240 | 235 | 190 | |
400375 | 280 | 250 | 200 | |
450400 | 300 | 270 | 215 | |
500425 | 320 | 290 | 230 | |
Conductor size—AWG1-3 conductor | 4-6 conductor | 7-9 conductor
1415 | 12 | 8
1220 | 16 | 11
1025 | 20 | 14
Conductor size—AWG or MCM3-conductor types G-GC and SIIC-GC 2,000 volts | 3-conductor type SHD-GC 2,001-5,000 volts
665 | 65
485 | 85
3100 | 100
2115 | 115
1130 | 130
1/0145 | 145
2/0170 | 170
3/0195 | 195
4/0220 | 220
250245 | 245
300275 | 275
350305 | 305
Conductor size—AWG or MCMSingle conductor | 2-conductor | 3-conductor | 4-conductor—Types W & G | 5-conductor—Types W & G | 6-conductor
Types W & G twistedType PG, 2 power | Type PCG, 3 power, ground | Types W & G | Type PG, 3 power, ground | Type PCG, 3 power, 2 control, ground | Type w | Tolerance
80.44 | 0.81 | 0.84 | 0.94 | 0.91 | 0.93 | 1.03 | 0.99 | 1.07 | 1.18 | ±0.03
60.51 | 0.93 | 0.93 | 0.98 | 1.01 | 1.03 | 1.18 | 1.1 | 1.21 | 1.31 | ±.03
40.57 | 1.08 | 1.08 | 1.1 | 1.17 | 1.2 | 1.29 | 1.27 | 1.4 | 1.52 | ±.03
30.63 | 1.17 | 1.17 | 1.2 | 1.24 | 1.27 | 1.31 | 1.34 | 1.48 | 1.61 | ±.03
20.66 | 1.27 | 1.27 | 1.29 | 1.34 | 1.34 | 1.39 | 1.48 | 1.61 | 1.75 | ±.03
10.74 | 1.44 | 1.44 | 1.44 | 1.51 | 1.52 | 1.52 | 1.68 | 1.88 | 2.05 | ±.03
1/00.77 | 1.52 | 1.52 | 1.52 | 1.65 | 1.68 | 1.68 | 1.79 | 1.96 | 2.13 | ±.04
2/00.82 | 1.65 | 1.65 | 1.65 | 1.75 | 1.79 | 1.79 | 1.93 | 2.13 | 2.32 | ±.04
3/00.87 | 1.77 | 1.77 | 1.77 | 1.89 | 1.93 | 1.93 | 2.07 | 2.26 | 2.49 | ±.05
4/00.93 | 1.92 | 1.92 | 1.92 | 2.04 | 2.13 | 2.13 | 2.26 | 2.46 | 2.71 | ±.05
2501.03 | 2.16 | 2.16 | 2.16 | 2.39 | 2.39 | 2.39 | 2.66 | | | ±.06
3001.09 | 2.32 | | | 2.56 | | | 2.84 | | | ±.06
3501.15 | 2.43 | | | 2.68 | | | 2.98 | | | ±.06
4001.2 | 2.57 | | | 2.82 | | | 3.14 | | | ±.06
4501.26 | 2.67 | | | 2.94 | | | 3.26 | | | ±.06
5001.31 | 2.76 | | | 3.03 | | | 3.4 | | | ±.06
Conductor size—AWG2-conductor | 3-conductor—Type G
Type WType G | Major | Minor
MajorMinor | Major | Minor | O.D. | Tolerance | O.D. | Tolerance
O.D.Tolerance | O.D. | Tolerance | O.D. | Tolerance | O.D. | Tolerance
80.84 | ±0.04 | 0.51 | ±0.03 | | | | | | | |
60.93 | ±.04 | 0.56 | ±.03 | 1.02 | ±.04 | 0.56 | ±.03 | 1.65 | ±0.06 | 0.67 | ±0.05
41.05 | ±.04 | 0.61 | ±.03 | 1.15 | ±.04 | 0.61 | ±.03 | 1.85 | ±.06 | 0.75 | ±.05
31.14 | ±.04 | 0.68 | ±.03 | 1.26 | ±.04 | 0.68 | ±.03 | 1.99 | ±.06 | 0.77 | ±.05
21.24 | ±.04 | 0.73 | ±.03 | 1.35 | ±.04 | 0.73 | ±.06 | 2.1 | ±.06 | 0.81 | ±.05
11.4 | ±.04 | 0.81 | ±.03 | 1.55 | ±.04 | 0.81 | ±.03 | 2.43 | ±.06 | 0.97 | ±.05
1/01.51 | ±.04 | 0.93 | ±.03 | 1.67 | ±.04 | 0.93 | ±.03 | | | |
2/01.63 | ±.04 | 0.99 | ±.03 | 1.85 | ±.04 | 0.99 | ±.03 | | | |
3/01.77 | ±.04 | 1.03 | ±.03 | 2 | ±.04 | 1.03 | ±.03 | | | |
4/01.89 | ±.04 | 1.1 | ±.03 | 2.1 | ±.04 | 1.1 | ±.03 | | | |
Conductor size—AWG2-conductor | 3-conductor | 4-conductor | 5-conductor | 6-conductor | 7-conductor
DiameterTolerance | Diameter | Tolerance | Diameter | Tolerance | Diameter | Tolerance | Diameter | Tolerance | Diameter | Tolerance
140.64 | ±0.02 | 0.67 | ±0.02 | 0.71 | ±0.02 | 0.78 | ±0.03 | 0.83 | ±0.03 | 0.89 | ±0.03
120.68 | ±.02 | 0.72 | ±.03 | 0.76 | ±.03 | 0.83 | ±.03 | 0.89 | ±.03 | 0.98 | ±.03
100.73 | ±.03 | 0.8 | ±.03 | 0.84 | ±.03 | 0.9 | ±.03 | 1 | ±.03 | 1.07 | ±.03
Conductor size—AWG or MCMType G-GC (nonshielded) 2,000 volts | Type SHC-GC (shielded overall) 2,000 volts | Type SHD-GC (individually shielded power conductors) 2,001-3,000 volts | Type SHD-GC (individually shielded power conductors) 3,001-5,000 volts
DiameterTolerance | Diameter | Tolerance | Diameter | Tolerance | Diameter | Tolerance
61.25 | + 0.10, −0.06 | 1.39 | + 0.11, −0.07 | 1.62 | + 0.13, −0.08 | 1.78 | + 0.14, −0.09
41.4 | + .11, −.07 | 1.55 | + .12, −.08 | 1.77 | + .14, −.09 | 1.9 | + .15, −.10
31.48 | + .12, −.07 | 1.62 | + .13, −.08 | 1.84 | + .15, −.09 | 1.98 | + .16, −.10
21.55 | + .12, −.08 | 1.71 | + .14, −.09 | 1.92 | + .15, −.10 | 2.09 | + .17, −.11
11.74 | + .14, −.09 | 1.89 | + .15, −.09 | 2.04 | + .16, −.10 | 2.18 | + .17, −.11
1/01.84 | + .15, −.09 | 2.02 | + .16, −.10 | 2.18 | + .17, −.11 | 2.34 | + .19, −.12
2/01.99 | + .16, −.10 | 2.16 | + .17, −.11 | 2.29 | + .18, −.12 | 2.46 | + .20, −.12
3/02.12 | + .17, −.11 | 2.3 | + .18, −.11 | 2.45 | + .20, −.12 | 2.62 | + .21, −.13
4/02.3 | + .18, −.12 | 2.48 | + .20, −.12 | 2.62 | + .21, −.13 | 2.76 | + .22, −.14
2502.46 | + .20, −.12 | 2.7 | + .22, −.13 | | | |
3002.63 | + .21, −.13 | 2.84 | + .23, −.14 | | | |
3502.75 | + .22, −.14 | 2.97 | + .24, −.15 | | | |
Conductor size—AWG or MCMOhms/1,000 ft. at 25 °C. | Maximum allowable fuse rating (amperes) | Maximum allowable circuit breaker instantaneous setting (amperes) 1
142.62 | 20 | 50
121.65 | 30 | 75
101.04 | 40 | 150
80.654 | 80 | 200
60.41 | 100 | 300
40.259 | 200 | 500
30.205 | 250 | 600
20.162 | 300 | 800
10.129 | 375 | 1,000
1/00.102 | 500 | 1,250
2/00.081 | | 1,500
3/00.064 | | 2,000
4/00.051 | | 2,500
2500.043 | | 2,500
3000.036 | | 2,500
3500.031 | | 2,500
4000.027 | | 2,500
4500.024 | | 2,500
5000.022 | | 2,500

1 Higher circuit-breaker settings may be permitted for special applications when justified.

Conductor size—AWG or MCMMax. allowable length (feet)Normal ampacity at 60 °C. copper temperature (40 °C. ambient)Resistance at 60 °C. copper temperature (ohms)
6550500.512
4600700.353
3650800.302
2700950.258
17501100.22
1/08001300.185
2/08501500.157
3/09001750.13
4/01,0002000.116
2501,0002200.098
3001,0002400.082
3501,0002600.07
4001,0002800.061
4501,0003000.054
5001,000320.050

1 Fuses shall not be used for short-circuit protection of these cables. Circuit breakers shall be used with the instantaneous trip settings not to exceed the values given in Table 8.

Power conductorAmpacity *Outside diameter **(inches)
Size AWG or kcmilAmperes per conductorSHD-GC 2001 to 5000 volts | SHD-CGC 2001 to 5000 volts | SHD-PCG 2001 to 5000 volts
6931.56 | 1.62 |
41221.68 | 1.73 |
31401.78 | 1.82 | 1.94
21591.87 | 1.91 | 2.03
11841.95 | 1.98 | 2.12
1/02112.08 | 2.1 | 2.26
2/02432.2 | 2.2 | 2.4
3/02792.36 | 2.36 | 2.58
4/03212.5 | 2.5 | 2.76
2503552.69 | 2.69 |
3003982.81 | 2.81 |
3504352.95 | 2.95 |
5005363.31 | 3.31 |

* These ampacities are based on single isolated conductor in air, operated with open-circuited shield for a 90 °C conductor temperature and an ambient temperature of 40 °C.

** Tolerances for the outside diameter are + 8%/−5%.

[33 FR 4660, Mar. 19, 1968; 33 FR 6345, Apr. 26, 1968, as amended at 42 FR 8373, Feb. 10, 1977; 75 FR 17549, Apr. 6, 2010; 75 FR 20918, Apr. 22, 2010]