33 CFR §127.1311
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
- (a)When LHG is being transferred or stored in the marine transfer area of a waterfront facility handling LHG, the operator must ensure that no person—
- (1)Stops or parks a motor vehicle in a space other than a designated parking space;
- (2)Refuels a motor vehicle within the area; or
- (3)Operates a vehicle or other mobile equipment that constitutes a potential source of ignition within 15 meters (49.2 feet) of any storage container, manifold, loading arm, or independent mating flange containing a flammable liquid or vapor.
- (b)If motor vehicles are permitted to stop in the marine transfer area for LHG, the operator shall designate and mark parking spaces that—