CFR › Title 33 › Part 127 › §127.20533 CFR §127.205Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗Copy linkEach transfer system must have an emergency shutdown system that—(a)Can be activated manually; and(b)Is activated automatically when the fixed sensors under § 127.201(b) measure LNG concentrations exceeding 40% of the lower flammable limit.