33 CFR §149.409

Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov
  1. (a)Approved portable and semi-portable extinguishers must be installed in accordance with table 149.409 of this section.
  2. (b)Semi-portable extinguishers must be located in the open so as to be readily seen.
  3. (c)Semi-portable extinguishers must be fitted so that all portions of the space concerned may be covered.
  4. (d)Table 149.409 of this section indicates the minimum required classification for each space listed. Extinguishers with larger numerical ratings or multiple letter designations may be used if the extinguishers meet the requirements of the table.
  5. (e)Semi-portable extinguishers must be fitted with a suitable hose and nozzle, or other practicable means, so that all areas of the space can be protected.