- (a)Each pumping platform complex must have a fixed fire main system. The system must either:
- (1)Comply with 46 CFR 108.415 through 108.429 and 33 CFR 127.607 if it is a natural gas deepwater port; or
- (2)Comply with a national consensus standard, as that term is defined in 29 CFR 1910.2, for such systems and hardware, and comply with the standards set by a nationally recognized testing laboratory, as that term is defined in 29 CFR 1910.7, for such systems and hardware.
- (b)If the fire main system meets the requirements outlined in paragraph (a)(2) of this section, it must provide, at a minimum, protection to:
- (c)The hose system must be capable of reaching all parts of these spaces without difficulty.
- (d)Under paragraph (a)(2) of this section, the fire main system may be part of a fire water system in accordance with 30 CFR 250.803.
- (e)A fire main system for a natural gas deepwater port must also comply with 33 CFR 127.607.