33 CFR §154.2109
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
Paragraphs (a), (b), and (e) of this section apply only to facilities collecting vapors of flammable, combustible, or non-high flash point liquid cargoes.
- (a)The inlet to a vapor recovery unit that receives vapor that has not been inerted, enriched, or diluted in accordance with 33 CFR 154.2107 must be fitted with a detonation arrester.
- (b)The inlet to a vapor destruction unit must—
- (1)Have a liquid seal that meets the requirements of paragraph (e) of this section, except as specified by paragraph (b)(3) of this section; and
- (2)Have two quick-closing stop valves installed in the vapor line. One of them must be installed upstream of the detonation arrester required by paragraph (c)(2) of this section. The quick-closing stop valves must—
- (i)Close within 30 seconds after detection of a condition that requires the closing of these two quick-closing stop valves by a control component required by this subpart for a vapor control system (VCS) with a vapor destruction unit;
- (ii)Close automatically if the control signal is lost;
- (iii)Have a local valve position indicator or be designed so that the valve position is readily determined from the valve handle or valve stem position; and
- (iv)If the valve seat is fitted with resilient material, be a Category A valve as defined by 46 CFR 56.20-15 and not allow appreciable leakage when the resilient material is damaged or destroyed; and
- (3)Instead of a liquid seal as required by paragraph (b)(1) of this section, have the following:
- (c)A vapor destruction unit must—
- (d)When a vapor destruction unit shuts down or has a flame-out condition, the vapor destruction unit control system must—
- (e)If a liquid seal is installed at the inlet to a vapor destruction unit, then—
- (1)The liquid used in the liquid seal must be compatible with the vapors being controlled;
- (2)For partially or totally soluble cargoes that can polymerize in solution, there must be an adequate amount of inhibitor in the liquid seal;
- (3)The liquid seal must be compatible with the design of the VCS and must not contribute to the flammability of the vapor stream; and
- (4)The liquid seal must have a low-level alarm and a low-low level shutdown.