33 CFR §183.516

Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov
  1. (a)Cellular plastic used to encase metallic fuel tanks must:
    1. (1)Not change volume by more than five percent or dissolve after being immersed in any of the following liquids for 24 hours at 29 °C:
      1. (i)Reference fuel B ASTM D 471 (incorporated by reference, see § 183.5).
      2. (ii)No. 2 reference oil of ASTM D 471 (incorporated by reference, see § 183.5).
      3. (iii)Five percent solution of trisodium phosphate in water; and
    2. (2)Not absorb more than 0.12 pound of water per square foot of cut surface, measure under Military Specification MIL P-21929B.
  2. (b)Non-polyurethane cellular plastic used to encase metallic fuel tanks must have a compressive strength of at least 60 pounds per square inch at ten percent deflection measured under ASTM D 1621 (incorporated by reference, see § 183.5), “Compressive Strength of Rigid Cellular Plastics”.
  3. (c)Polyurethane cellular plastic used to encase metallic fuel tanks must have a density of at least 2.0 pounds per cubic foot, measured under ASTM D 1622 (incorporated by reference, see § 183.5), “Apparent Density of Rigid Cellular Plastics.”