- (a)Except for compartments open to the atmosphere, a natural ventilation system that meets the requirements of § 183.630 must be provided for each compartment in a boat that:
- (1)Contains a permanently installed gasoline engine;
- (2)Has openings between it and a compartment that requires ventilation, where the aggregate area of those openings exceeds 2 percent of the area between the compartments, except as provided in paragraph (c) of this section;
- (3)Contains a permanently installed fuel tank and an electrical component that is not ignition protected in accordance with § 183.410(a);
- (4)Contains a fuel tank that vents into that compartment; or
- (5)Contains a non-metallic fuel tank:
- (b)Each supply opening required in § 183.630 must be located on the exterior surface of the boat.
- (c)An accommodation compartment above a compartment requiring ventilation that is separated from the compartment requiring ventilation by a deck or other structure is excepted from paragraph (a)(2) of this section.