49 CFR §192.167
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
- (a)Except for unattended field compressor stations of 1,000 horsepower (746 kilowatts) or less, each compressor station must have an emergency shutdown system that meets the following:
- (1)It must be able to block gas out of the station and blow down the station piping.
- (2)It must discharge gas from the blowdown piping at a location where the gas will not create a hazard.
- (3)It must provide means for the shutdown of gas compressing equipment, gas fires, and electrical facilities in the vicinity of gas headers and in the compressor building, except that:
- (4)It must be operable from at least two locations, each of which is:
- (b)If a compressor station supplies gas directly to a distribution system with no other adequate source of gas available, the emergency shutdown system must be designed so that it will not function at the wrong time and cause an unintended outage on the distribution system.
- (c)On a platform located offshore or in inland navigable waters, the emergency shutdown system must be designed and installed to actuate automatically by each of the following events: