(a) General. Each manufactured home must be designed and constructed as a completely integrated structure capable of sustaining the design load requirements of this part and must be capable of transmitting these loads to stabilizing devices without exceeding the allowable stresses or deflections. Roof framing must be securely fastened to wall framing, walls to floor structure, and floor structure to chassis to secure and maintain continuity between the floor and chassis, so as to resist wind overturning, uplift, and sliding as imposed by design loads in this part. In multistory construction, each story must be securely fastened to the story above and/or below to provide continuity and resist design loads in this part. Uncompressed finished flooring greater than 1⁄8 inch in thickness must not extend beneath load-bearing walls that are fastened to the floor structure.
* * * * *
(e) * * *
(1) Roof framing must be securely fastened to wall framing, walls to floor structure, and floor structure to chassis, to secure and maintain continuity between the floor and chassis in order to resist wind overturning, uplift, and sliding, and to provide continuous load paths for these forces to the foundation or anchorage system. The number and type of fasteners used must be capable of transferring all forces between elements being joined. In multistory construction, each story must be securely fastened to the story above and/or below to provide continuity and resist design loads in this section.
* * * * *
(g) * * *
(6) Bottom board material (with or without patches) must meet or exceed the level of 48 inch-pounds of puncture resistance as tested by the Beach Puncture Test in accordance with Standard Test Methods for Puncture and Stiffness of Paperboard, and Corrugated and Solid Fiberboard, ASTM D781-1968 (Reapproved 1973) (incorporated by reference, see §3280.4). The material must be suitable for patches and the patch life must be equivalent to the material life. Patch installation instruction must be included in the manufactured home manufacturer's instructions. The bottom board material must be tight fitted against all penetrations.
(h) * * *
(5) Portions of roof assemblies, including, but not limited to, dormers, gables, crickets, hinged roof sections, sheathing, roof coverings, underlayments, flashings, and eaves and overhangs are permitted to be assembled and installed on site in accordance with 24 CFR part 3282, subpart M, provided that the requirements in paragraphs (h)(5)(i) through (v) of this section are met.
(i) Approved installation instructions must be provided that include requirements for the following items:
(A) Materials, installation, and structural connections complying with this section;
(B) Installation and fastening of sheathing and roof coverings;
(C) Installation of appliance vent systems in accordance with §3280.710;
(D) Installation of plumbing vents as required by §3280.611; and
(E) Installation of attic ventilation in accordance with §3280.504(c).
(ii) The installation instructions specified in paragraph (h)(5)(i) of this section must include drawings, details, and instructions as necessary to assure that the on-site work complies with the approved design.
(iii) The installation instructions specified in paragraph (h)(5)(i) of this section must provide for inspection of the work at the installation site. As necessary to ensure conformance, inspection panels may be required, or inspections may need to occur in stages that assure inspections are performed before any work is concealed. Such inspection procedures shall be addressed in the approved installation instructions.
(iv) Temporary weather protection must be provided per §3280.307(e).
* * * * *
Need assistance?