40 CFR § 417.123
Effluent limitations guidelines representing the degree of effluent reduction attainable by the application of the best available technology economically achievable
June 9, 2020
CFR

The following limitations establish the quantity or quality of pollutants or pollutant properties, controlled by this section, which may be discharged by a point source subject to the provisions of this subpart after application of the best available technology economically achievable:

Open Table
Effluent characteristic Effluent limitations
Maximum for any 1 day Average of daily values for 30 consecutive days shall not exceed—
Metric units (kilograms per 1,000 kg of anhydrous product)
BOD5 0.20 0.10
COD 0.90 .48
TSS 0.02 .01
Surfactants 0.20 .10
Oil and grease 0.04 .02
pH (1) (1)
English units (pounds per 1,000 lb of anhydrous product)
BOD5 0.20 0.10
COD 0.90 .48
TSS 0.02 .01
Surfactants 0.20 .10
Oil and grease 0.04 .02
pH (1) (1)

1Within the range 6.0 to 9.0.