40 CFR § 420.17
Effluent limitations representing the degree of effluent reduction attainable by the application of the best conventional technology (BCT)
June 9, 2020
CFR

Except as provided in 40 CFR 125.30 through 125.32, any existing point source subject to this subpart must achieve the following effluent limitations representing the degree of effluent reduction attainable by the application of the best conventional technology.

(a) By-product cokemaking—iron and steel.

Subpart A

Open Table
Pollutant or pollutant property BCT effluent limitations
Maximum for any 1 day Average of daily values for 30 consecutive days
Kg/kkg (pounds per 1,000 lb) of product
TSS 0.253 0.131
O&G 0.0327 0.0109
pH (1) (1)

1Within the range of 6.0 to 9.0.

(1) Increased loadings, not to exceed 11 percent of the above limitations, are allowed for by-product coke plants which have wet desulfurization systems but only to the extent such systems generate an increased effluent volume.

(2) Increased loadings, not to exceed 27 percent of the above limitations, are allowed for by-product coke plants which include indirect ammonia recovery systems but only to the extent that such systems generate an increased effluent volume.

(b) By-product cokemaking—merchant.

Subpart A

Open Table
Pollutant or pollutant property BCT effluent limitations
Maximum for any 1 day Average of daily values for 30 consecutive days
Kg/kkg (pounds per 1,000 lb) of product
TSS 0.270 0.140
O&G 0.0348 0.0116
pH (1) (1)

1Within the range of 6.0 to 9.0.

(1) Increased loadings, not to exceed 10 percent of the above limitations, are allowed for by-product coke plants which have wet desulfurization systems but only to the extent such systems generate an increased effluent volume.

(2) Increased loadings, not to exceed 25 percent of the above limitations, are allowed for by-product coke plants which include indirect ammonia recovery systems but only to the extent that such systems generate an increased effluent volume.

(c) Cokemaking—non-recovery. Except as provided in 40 CFR 125.30 through 125.32, any existing point source subject to this segment must achieve the following effluent limitations representing the degree of effluent reduction attainable by the application of the best conventional pollutant control technology (BCT): There shall be no discharge of process wastewater pollutants to waters of the U.S.

[47 FR 23284, May 27, 1982, as amended at 67 FR 64264, Oct. 17, 2002]