(a) For owners or operators of an affected source that are using add-on air pollution control equipment or a steam stripper to comply with §63.703, paragraph (b) of this section identifies the operating parameter to be monitored to demonstrate continuous compliance. For all owners or operators subject to §63.703, except §63.703(b) and (h), regardless of the type of control technique used, paragraph (c) of this section identifies the procedures that must be followed to demonstrate continuous compliance with §63.703.
(b) Establishing a limit under §63.703(i) and operating parameter values. The owner or operator of an affected source subject to §63.703 except §63.703(b) and (h), shall establish the operating parameter value to be monitored for compliance as required by paragraph (c) of this section, in accordance with paragraphs (b)(1) through (b)(11) of this section. An owner or operator subject to §63.703(i) shall establish a limit as required in paragraph (b)(11)(ii) of this section.
(1) Except as allowed by paragraphs (b)(2), (3), (4), (5), or (9) of this section, for each add-on air pollution control device used to control solvent HAP emissions, the owner or operator shall fulfill the requirements of paragraph (b)(1)(i) or (ii) of this section.
(i) The owner or operator shall establish as a site-specific operating parameter the outlet total HAP or VOC concentration that demonstrates compliance with §63.703(c)(1), (c)(2), (c)(4), (e)(1)(i), (f)(1)(i), or (i) as appropriate; or
(ii) The owner or operator shall establish as the site-specific operating parameter the control device efficiency that demonstrates compliance with §63.703(c)(1), (c)(4), (e)(1)(i), and (f)(1)(i).
(iii) When a nonregenerative carbon adsorber is used to comply with §63.703(c)(1), the site-specific operating parameter value may be established as part of the design evaluation used to demonstrate initial compliance (§63.705(c)(6)). Otherwise, the site-specific operating parameter value shall be established during the initial performance test conducted according to the procedures of §63.705(c)(1), (2), (3), or (4).
(2) For each condenser used as the add-on air pollution control device to comply with §63.703(c), (e)(1)(i), (f)(1)(i) or (i), in lieu of meeting the requirements of §63.704(b)(1), during the initial performance test conducted according to the procedures of §63.705(c)(1), (2), or (4), the owner or operator may establish as a site-specific operating parameter the maximum temperature of the condenser vapor exhaust stream and shall set the operating parameter value that demonstrates compliance with §63.703(c), (e)(1)(i), (f)(1)(i) or (i) as appropriate;
(3) For each thermal incinerator, in lieu of meeting the requirements of §63.704(b)(1), during the initial performance test conducted according to the procedures of §63.705(c)(1), (2), or (4), the owner or operator may establish as a site-specific operating parameter the minimum combustion temperature and set the operating parameter value that demonstrates compliance with §63.703(c), (e)(1)(i), or (f)(1)(i), as appropriate.
(4) For each catalytic incinerator, in lieu of meeting the requirements of §63.704(b)(1), during the initial performance test conducted according to the procedures of §63.705(c)(1), (2), or (4), the owner or operator may establish as site-specific operating parameters the minimum gas temperature upstream of the catalyst bed and the minimum gas temperature difference across the catalyst bed, and set the operating parameter values that demonstrate compliance with §63.703(c), (e)(1)(i), or (f)(1)(i), as appropriate.
(5) For each nonregenerative carbon adsorber, in lieu of meeting the requirements of §63.704(b)(1), the owner or operator may establish as the site-specific operating parameter the carbon replacement time interval, as determined by the maximum design flow rate and organic concentration in the gas stream vented to the carbon adsorption system. The carbon replacement time interval shall be established either as part of the design evaluation to demonstrate initial compliance (§63.705(c)(6)), or during the initial performance test conducted according to the procedures of §63.705(c)(1), (2), (3), or (4).
(6) Each owner or operator venting solvent HAP emissions from a source through a room, enclosure, or hood, to a control device to comply with §63.703(c), (e)(1)(i), (f)(1)(i), or (i) shall:
(i) Submit to the Administrator with the compliance status report required by §63.9(h) of the General Provisions a plan that:
(A) Identifies the operating parameter to be monitored to ensure that the capture efficiency measured during the initial compliance test is maintained;
(B) Discusses why this parameter is appropriate for demonstrating ongoing compliance; and
(C) Identifies the specific monitoring procedures;
(ii) Set the operating parameter value, or range of values, that demonstrate compliance with §63.703(c), (e)(1)(i), (f)(1)(i), or (i), as appropriate; and
(iii) Conduct monitoring in accordance with the plan submitted to the Administrator unless comments received from the Administrator require an alternate monitoring scheme.
(7) For each baghouse or fabric filter used to control particulate HAP emissions in accordance with §63.703(d)(2), the owner or operator shall establish as the site-specific operating parameter the minimum ventilation air flow rate through the inlet duct to the baghouse or fabric filter that ensures that particulate HAP are being captured and delivered to the control device. The minimum ventilation air flow rate is to be supported by the engineering calculations that are considered part of the initial performance test, as required by §63.705(g)(2).
(8) Owners or operators subject to §63.704(b)(1), (2), (3), (4), (5), (6), or (7) shall calculate the site-specific operating parameter value, or range of values, as the arithmetic average of the maximum and/or minimum operating parameter values, as appropriate, that demonstrate compliance with §63.703(c), (d), (e), (f) or (i) during the multiple test runs required by §63.705(b)(2) and (b)(1), or during the multiple runs of other tests conducted as allowed by paragraph §63.704(b)(11).
(9) For each solvent recovery device used to comply with §63.703(c), in lieu of meeting the requirements of paragraph (b)(1) of this section, the results of the material balance calculation conducted in accordance with §63.705(c)(1) may serve as the site-specific operating parameter that demonstrates compliance with §63.703(c).
(10) Owners or operators complying with the provisions of §63.703(g) shall establish the site-specific operating parameter according to paragraph (b)(10)(i) or (ii) of this section.
(i) Owners or operators using a steam stripper shall establish the steam-to-feed ratio as the site-specific operating parameter, except as allowed in paragraph (b)(10)(ii) of this section, according to the following criteria:
(A) The minimum operating parameter value shall correspond to at least the fraction removed specified in §63.703(g)(1)(i) and be submitted to the permitting authority for approval with the design specifications required by §63.705(h)(1); or
(B) The minimum operating parameter value shall be that value that corresponds to a total VOHAP outlet concentration in the wastewater of less than 50 ppmw as determined through tests conducted in accordance with §63.705(b)(9) and (h)(2); or
(C) The minimum operating parameter value shall be the value that corresponds to at least the fraction removed specified in §63.705(g)(1)(i), as demonstrated through tests conducted in accordance with §63.705(b)(9) and (h)(3).
(ii) Owners or operators complying with §63.703(g) through the use of a steam stripper or any other control technique may establish as a site-specific operating parameter the outlet total VOHAP concentration according to the following criteria:
(A) The minimum operating parameter value shall correspond to at least the fraction removed specified in §63.703(g)(1)(i) and be submitted to the permitting authority for approval with the design specifications required by §63.705(h)(1); or
(B) The minimum operating parameter value shall be a total VOHAP outlet concentration in the wastewater of less than 50 ppmw, as required by §63.703(g)(1)(ii), and as determined through tests conducted in accordance with §63.705 (b)(9) and (h)(2); or
(C) The minimum operating parameter value shall be the value that corresponds to at least the fraction removed specified in §63.705(g)(1)(i), as demonstrated through tests conducted in accordance with §63.705 (b)(9) and (h)(3).
(11) Compliance provisions for nonrepresentative operating conditions.
(i) The owner or operator of an affected source may conduct multiple performance tests to establish the operating parameter value, or range of values, that demonstrates compliance with the standards in §63.703 during various operating conditions.
(ii) To establish an alternate outlet concentration limit as provided in §63.703(i), the owner or operator, when the coating operation is not occurring, shall conduct a performance test using the methods in §63.705 for determining initial compliance with §63.703 (c)(1), (e)(1)(i) or (f)(1)(i), or shall collect data from continuous emission monitors used to determine continuous compliance as specified in §63.704 (b) and (c). During the period in which this limit is being established, the control device shall be operated in accordance with good air pollution control practices and in the same manner as it was operated to achieve the emission limitation for coating operations. Owners or operators choosing to establish such an alternative shall also comply with paragraphs (b)(11)(ii) (A) and (B) of this section.
(A) The owner or operator shall submit the alternate outlet HAP concentration limit within 180 days after the compliance demonstration required by §63.7 of subpart A, to the Administrator, as required by §63.707(k)(1).
(B) The Administrator will approve or disapprove the limit proposed in accordance with paragraph (b)(11)(ii)(A) of this section within 60 days of receipt of the report required by §63.707(k)(1), and any other supplemental information requested by the Administrator to support the alternate limit.
(c) Continuous compliance monitoring. Following the date on which the initial compliance demonstration is completed, continuous compliance with the standards shall be demonstrated as outlined in paragraphs (c), (d), (e), or (f) of this section.
(1)
(i) Each owner or operator of an affected source subject to §63.703 (c)(1), (c)(2), (c)(3), (c)(4), (e)(1)(i), (f)(1)(i), or (i) of this subpart shall monitor the applicable parameters specified in paragraphs (c)(3), (4), (5), (6), (7), or (9) of this section depending on the type of control technique used, and shall monitor the parameters specified in paragraph (c)(10) of this section.
(ii) Each owner or operator of an affected source subject to §63.703(c)(5) of this subpart shall demonstrate continuous compliance as required by paragraph (c)(8) of this section.
(iii) Each owner or operator of an affected source subject to §63.703(d)(2) of this subpart shall demonstrate continuous compliance as required by paragraph (e) of this section.
(iv) Each owner or operator of an affected source subject to §63.703(g) of this subpart shall demonstrate continuous compliance as required by paragraph (d) of this section.
(2) Compliance monitoring shall be subject to the following provisions.
(i) Except as allowed by paragraph (c)(3)(i)(C) of this section, all continuous emission monitors shall comply with performance specification (PS) 8 or 9 in 40 CFR part 60, appendix B, as appropriate depending on whether volatile organic compound (VOC) or HAP concentration is being measured. The requirements in appendix F of 40 CFR part 60 shall also be followed. In conducting the quarterly audits required by appendix F, owners or operators must challenge the monitors with compounds representative of the gaseous emission stream being controlled.
(ii) All temperature monitoring equipment shall be installed, calibrated, maintained, and operated according to the manufacturer's specifications. The thermocouple calibration shall be verified or replaced every 3 months. The replacement shall be done either if the owner or operator chooses not to calibrate the thermocouple, or if the thermocouple cannot be properly calibrated.
(iii) If the effluent from multiple emission points are combined prior to being channeled to a common control device, the owner or operator is required only to monitor the common control device, not each emission point.
(3) Owners or operators complying with §63.703(c), (e)(1)(i), (f)(1)(i), or (i) through the use of a control device and establishing a site-specific operating parameter in accordance with §63.704(b)(1) shall fulfill the requirements of paragraphs (c)(3)(i) of this section and paragraph (c)(3)(ii), (iii), (iv), or (v) of this section, as appropriate.
(i) The owner or operator shall install, calibrate, operate, and maintain a continuous emission monitor.
(A) The continuous emission monitor shall be used to measure continuously the total HAP or VOC concentration at both the inlet and the outlet whenever HAP from magnetic tape manufacturing operations are vented to the control device, if continuous compliance is demonstrated through a percent efficiency calculation (§63.704(b)(1)(ii)); or
(B) The continuous emission monitor shall be used to measure continuously the total outlet HAP or VOC concentration whenever HAP from magnetic tape manufacturing operations are vented to the control device, if the provisions of §63.704(b)(1)(i) are being used to determine continuous compliance.
(C) For owners or operators using a nonregenerative carbon adsorber, in lieu of using continuous emission monitors as specified in paragraph (c)(3)(i) (A) or (B) of this section, the owner or operator may use a portable monitoring device to monitor total HAP or VOC concentration at the inlet and outlet, or outlet of the carbon adsorber, as appropriate.
(1) The monitoring device shall be calibrated, operated, and maintained in accordance with the manufacturer's specifications.
(2) The monitoring device shall meet the requirements of part 60, appendix A, method 21, sections 2, 3, 4.1, 4.2, and 4.4. For the purposes of paragraph (c)(3)(i)(C) of this section, the words “leak definition” in method 21 shall be the outlet concentration determined in accordance with §63.704(b)(1). The calibration gas shall either be representative of the compounds to be measured or shall be methane, and shall be at a concentration associated with 125 percent of the expected organic compound concentration level for the carbon adsorber outlet vent.
(3) The probe inlet of the monitoring device shall be placed at approximately the center of the carbon adsorber outlet vent. The probe shall be held there for at least 5 minutes during which flow into the carbon adsorber is expected to occur. The maximum reading during that period shall be used as the measurement.
(ii) If complying with §63.703 (c)(1), (c)(3), (c)(4), (e)(1)(i), (f)(1)(i), or (i) through the use of a carbon adsorption system with a common exhaust stack for all of the carbon vessels, the owner or operator shall not operate the control device at an average control efficiency less than that required by §63.703 (c)(1), (c)(3), (c)(4), (e)(1)(i), or (f)(1)(i) or at an average outlet concentration exceeding the site-specific operating parameter value or that required by §63.703(i), for three consecutive adsorption cycles. Operation in this manner shall constitute a violation of §63.703 (c)(1), (c)(3), (c)(4), (e)(1)(i), (f)(1)(i), or (i).
(iii) If complying with §63.703 (c)(1), (c)(3), (c)(4), (e)(1)(i), (f)(1)(i), or (i) through the use of a carbon adsorption system with individual exhaust stacks for each of the multiple carbon adsorber vessels, the owner or operator shall not operate any carbon adsorber vessel at an average control efficiency less than that required by §63.703 (c)(1), (c)(3), (c)(4), (e)(1)(i), or (f)(1)(i), or at an average outlet concentration exceeding the site-specific operating parameter value or that required by §63.703(i), as calculated daily using a 3-day rolling average. Operation in this manner shall constitute a violation of §63.703 (c)(1), (c)(3), (c)(4), (e)(1)(i), (f)(1)(i), or (i).
(iv) If complying with §63.703 (c)(1), (c)(2), (c)(3), (c)(4), (e)(1)(i), (f)(1)(i), or (i) through the use of any control device other than a carbon adsorber, the owner or operator shall not operate the control device at an average control efficiency less than that required by §63.703 (c)(1), (c)(3), (c)(4), (e)(1)(i), or (f)(1)(i), or at an average outlet concentration exceeding the site-specific operating parameter value or that required by §63.703(c)(2) or (i), as calculated for any 3-hour period. Operation in this manner shall constitute a violation of §63.703 (c)(1), (c)(2), (c)(3), (c)(4), (e)(1)(i), (f)(1)(i), or (i).
(v) If complying with §63.703(c)(1) through the use of a nonregenerative carbon adsorber, in lieu of the requirements of paragraphs (c)(3) (ii) or (iii) of this section, the owner or operator may:
(A) monitor the VOC or HAP concentration of the adsorber exhaust daily or at intervals no greater than 20 percent of the design carbon replacement interval, whichever is greater; operation of the control device at a HAP or VOC concentration greater than that determined in accordance with §63.704(b)(1)(iii) shall constitute a violation of §63.703 (c)(1), (e)(1)(i), or (f)(1)(i); or
(B) replace the carbon in the carbon adsorber system with fresh carbon at a regular predetermined time interval as determined in accordance with §63.704(b)(5); failure to replace the carbon at this predetermined time interval shall constitute a violation of §63.703 (c)(1), (e)(1)(i), or (f)(1)(i).
(4) Owners or operators complying with §63.703 (c)(1), (c)(3), (c)(4), (e)(1)(i), (f)(1)(i), or (i) through the use of a condenser as the add-on air pollution control device, and demonstrating compliance in accordance with §63.704(b)(2), shall install, calibrate, operate, and maintain a thermocouple to measure continuously the temperature of the condenser vapor exhaust stream whenever HAP from magnetic tape manufacturing operations are vented to the control device. Operation of the control device at an average vapor exhaust temperature greater than the site-specific operating parameter value or values established in accordance with §63.704(b)(2) for any 3-hour period shall constitute a violation of §63.703 (c)(1), (c)(3), (c)(4), (e)(1)(i), (f)(1)(i) or (i).
(5) Owners or operators complying with §63.703 (c)(1), (c)(2), (c)(3), (c)(4), (e)(1)(i), or (f)(1)(i) through the use of a thermal incinerator and demonstrating compliance in accordance with §63.704(b)(3) shall install, calibrate, operate, and maintain a thermocouple to measure continuously the combustion temperature whenever HAP from magnetic tape manufacturing operations are vented to the control device. Operation of the control device at an average combustion temperature less than the operating parameter value or values established in accordance with §63.704(b)(3) for any 3-hour period shall constitute a violation of §63.703 (c)(1), (c)(2), (c)(3), (c)(4), (e)(1)(i), or (f)(1)(i).
(6) Owners or operators complying with §63.703 (c)(1), (c)(2), (c)(3), (c)(4), (e)(1)(i), or (f)(1)(i) through the use of a catalytic incinerator and demonstrating compliance in accordance with §63.704(b)(4) shall install, calibrate, operate, and maintain a thermocouple to measure continuously the gas temperature both upstream and downstream of the catalyst bed whenever HAP from magnetic tape manufacturing operations are vented to the control device. Operation of the control device at an average upstream gas temperature, or at an average gas temperature difference across the catalyst bed, less than the operating parameter values established in accordance with §63.704(b)(4) for any 3-hour period shall constitute a violation of §63.703 (c)(1), (c)(2), (c)(3), (c)(4), (e)(1)(i), or (f)(1)(i).
(7) Owners or operators complying with §63.703 (c)(1), (c)(2), (c)(3), (c)(4), (e)(1)(i), (f)(1)(i), or (i) by capturing emissions through a room, enclosure, or hood shall install, calibrate, operate, and maintain the instrumentation necessary to measure continuously the site-specific operating parameter established in accordance with §63.704(b)(6) whenever HAP from magnetic tape manufacturing operations are vented through the capture device. Operation of the capture device at an average value greater than or less than (as appropriate) the operating parameter value established in accordance with §63.704(b)(6) for any 3-hour period shall constitute a violation of §63.703 (c)(1), (c)(2), (c)(3), (c)(4), (e)(1)(i), (f)(1)(i), or (i).
(8) The owner or operator of an affected source complying with §63.703(c)(5) shall demonstrate continuous compliance by using a coating that has a HAP content of no greater than 0.18 kilograms of HAP per liter of coating solids, as measured in accordance with §63.705(c)(5), and by maintaining and reporting the records required by §§63.706(f) and 63.707(e) and (i)(2).
(9) For owners or operators complying with §63.703 (c)(1), (c)(3), or (c)(4) through the use of a solvent recovery device and demonstrating initial compliance in accordance with the provisions of §63.705(c)(1), continuous compliance shall be demonstrated using procedures in §63.705(c)(1) and through the recordkeeping and reporting requirements of §§63.706(d), 63.707(d), and 63.707(i)(5). The provisions of §63.8(b) (2) and (3), (c), (d), (e), (f), and (g) (1), and (2) of subpart A do not apply.
(10) The owner or operator of an affected emission point using a vent system that contains bypass lines (not including equipment such as low leg drains, high point bleeds, analyzer vents, open-ended valves or lines, and pressure relief valves needed for safety purposes) that could potentially divert a vent stream away from the control device used to comply with §63.703 (c)(1), (c)(2), (c)(3), (c)(4), (e)(1)(i), (f)(1)(i), or (i) shall:
(i) Install, calibrate, maintain, and operate a flow indicator that provides a record of vent stream flow at least once every 15 minutes; records shall be generated as specified in §63.706(c)(1); and the flow indicator shall be installed at the entrance to any bypass line that could divert the vent stream away from the control device to the atmosphere; or
(ii) Secure any bypass line valve in the closed position with a car-seal or a lock-and-key type configuration; a visual inspection of the seal or closure mechanism shall be performed at least once every month to ensure that the valve is maintained in the closed position and the vent stream is not diverted through the bypass line; or
(iii) Ensure that any bypass line valve is in the closed position through continuous monitoring of valve position; the monitoring system shall be inspected at least once every month to ensure that it is functioning properly; or
(iv) Use an automatic shutdown system in which any HAP-emitting operations are ceased when flow from these operations is diverted away from the control device to any bypass line; the automatic system shall be inspected at least once every month to ensure that it is functioning properly.
(d) Owners or operators complying with §63.703(g) shall demonstrate continuous compliance in accordance with paragraph (d)(1) or (d)(2) of this section.
(1) An owner or operator that established the steam-to-feed ratio as the site-specific operating parameter in accordance with §63.704(b)(10)(i) shall continuously measure the steam-to-feed ratio whenever HAP-containing wastewater from magnetic tape manufacturing operations is being fed to the steam stripper. Operation of the steam stripper at a steam-to-feed ratio less than the operating parameter value or values established in accordance with §63.704(b)(10)(i) for any 3-hour period shall constitute a violation of §63.703(g).
(2) An owner or operator that established the total outlet VOHAP concentration of the wastewater discharge as the site-specific operating parameter in accordance with §63.704(b)(10)(ii) shall measure the total VOHAP concentration of the wastewater discharge once per month. Operation of the control device at an outlet VOHAP concentration greater than the operating parameter value or values established in accordance with §63.704(b)(10)(ii) for any month shall constitute a violation of §63.703(g).
(e) Owners or operators complying with §63.703(d)(2) of this subpart through the use of a baghouse or fabric filter shall perform visible emission testing each day that particulate HAP transfer occurs, using the procedures in §63.705(b)(10). Owners or operators shall also install, calibrate, and operate the instrumentation necessary to continuously monitor the ventilation air flow rate in the inlet duct to the baghouse or fabric filter whenever particulate HAP transfer occurs. The occurrence of visible emissions shall constitute a violation of §63.703(d)(2), and the operation of the baghouse or fabric filter at a flow rate less than the value or values established in accordance with §63.704(b)(7) for any 3-hour period shall constitute a violation of §63.703(d)(2).
(f) An owner or operator who uses an air pollution control device not listed in §63.704 to comply with §63.703(c), (e)(1)(i), (f)(1)(i), or (i), or a device other than a steam stripper to comply with §63.703(g) shall submit to the Administrator a description of the device, test data verifying the performance of the device, and appropriate site-specific operating parameters that will be monitored to demonstrate continuous compliance with the standard. The monitoring plan submitted by an owner or operator in accordance with this paragraph is subject to approval by the Administrator.