As stated in §63.9991, you must comply with the following applicable emission limits:1

Open Table
If your EGU is in this subcategory .  .  . For the following
pollutants .  .  .
You must meet the following emission limits and work practice
standards .  .  .
Using these requirements, as appropriate (e.g., specified sampling volume or test run duration) and limitations with the test methods in Table 5 to this Subpart .  .  .
1. Coal-fired unit not low rank virgin coal a. Filterable particulate matter (PM) 3.0E-2 lb/MMBtu or 3.0E-1 lb/MWh2 Collect a minimum of 1 dscm per run.
    OR OR
    Total non-Hg HAP metals 5.0E-5 lb/MMBtu or 5.0E-1 lb/GWh Collect a minimum of 1 dscm per run.
    OR OR
    Individual HAP metals: Collect a minimum of 3 dscm per run.
    Antimony (Sb) 8.0E-1 lb/TBtu or 8.0E-3 lb/GWh
    Arsenic (As) 1.1E0 lb/TBtu or 2.0E-2 lb/GWh
    Beryllium (Be) 2.0E-1 lb/TBtu or 2.0E-3 lb/GWh
    Cadmium (Cd) 3.0E-1 lb/TBtu or 3.0E-3 lb/GWh
    Chromium (Cr) 2.8E0 lb/TBtu or 3.0E-2 lb/GWh
    Cobalt (Co) 8.0E-1 lb/TBtu or 8.0E-3 lb/GWh
    Lead (Pb) 1.2E0 lb/TBtu or 2.0E-2 lb/GWh
    Manganese (Mn) 4.0E0 lb/TBtu or 5.0E-2 lb/GWh
    Nickel (Ni) 3.5E0 lb/TBtu or 4.0E-2 lb/GWh
    Selenium (Se) 5.0E0 lb/TBtu or 6.0E-2 lb/GWh
    b. Hydrogen chloride (HCl) 2.0E-3 lb/MMBtu or 2.0E-2 lb/MWh For Method 26A at appendix A-8 to part 60 of this chapter, collect a minimum of 0.75 dscm per run; for Method 26, collect a minimum of 120 liters per run. For ASTM D6348-033 or Method 320 at appendix A to part 63 of this chapter, sample for a minimum of 1 hour.
    OR
    Sulfur dioxide (SO2)4 2.0E-1 lb/MMBtu or 1.5E0 lb/MWh SO2 CEMS.
    c. Mercury (Hg) 1.2E0 lb/TBtu or 1.3E-2 lb/GWh LEE Testing for 30 days with a sampling period consistent with that given in section 5.2.1 of appendix A to this subpart per Method 30B at appendix A-8 to part 60 of this chapter run or Hg CEMS or sorbent trap monitoring system only.
    OR
    1.0E0 lb/TBtu or 1.1E-2 lb/GWh LEE Testing for 90 days with a sampling period consistent with that given in section 5.2.1 of appendix A to this subpart per Method 30B run or Hg CEMS or sorbent trap monitoring system only.
2. Coal-fired unit low rank virgin coal a. Filterable particulate matter (PM) 3.0E-2 lb/MMBtu or 3.0E-1 lb/MWh2 Collect a minimum of 1 dscm per run.
    OR OR
    Total non-Hg HAP metals 5.0E-5 lb/MMBtu or 5.0E-1 lb/GWh Collect a minimum of 1 dscm per run.
    OR OR
    Individual HAP metals: Collect a minimum of 3 dscm per run.
    Antimony (Sb) 8.0E-1 lb/TBtu or 8.0E-3 lb/GWh
    Arsenic (As) 1.1E0 lb/TBtu or 2.0E-2 lb/GWh
    Beryllium (Be) 2.0E-1 lb/TBtu or 2.0E-3 lb/GWh
    Cadmium (Cd) 3.0E-1 lb/TBtu or 3.0E-3 lb/GWh
    Chromium (Cr) 2.8E0 lb/TBtu or 3.0E-2 lb/GWh
    Cobalt (Co) 8.0E-1 lb/TBtu or 8.0E-3 lb/GWh
    Lead (Pb) 1.2E0 lb/TBtu or 2.0E-2 lb/GWh
    Manganese (Mn) 4.0E0 lb/TBtu or 5.0E-2 lb/GWh
    Nickel (Ni) 3.5E0 lb/TBtu or 4.0E-2 lb/GWh
    Selenium (Se) 5.0E0 lb/TBtu or 6.0E-2 lb/GWh
    b. Hydrogen chloride (HCl) 2.0E-3 lb/MMBtu or 2.0E-2 lb/MWh For Method 26A, collect a minimum of 0.75 dscm per run; for Method 26 at appendix A-8 to part 60 of this chapter, collect a minimum of 120 liters per run. For ASTM D6348-033 or Method 320, sample for a minimum of 1 hour.
    OR
    Sulfur dioxide (SO2)4 2.0E-1 lb/MMBtu or 1.5E0 lb/MWh SO2 CEMS.
    c. Mercury (Hg) 4.0E0 lb/TBtu or 4.0E-2 lb/GWh LEE Testing for 30 days with a sampling period consistent with that given in section 5.2.1 of appendix A to this subpart per Method 30B run or Hg CEMS or sorbent trap monitoring system only.
3. IGCC unit a. Filterable particulate matter (PM) 4.0E-2 lb/MMBtu or 4.0E-1 lb/MWh2 Collect a minimum of 1 dscm per run.
    OR OR
    Total non-Hg HAP metals 6.0E-5 lb/MMBtu or 5.0E-1 lb/GWh Collect a minimum of 1 dscm per run.
    OR OR
    Individual HAP metals: Collect a minimum of 2 dscm per run.
    Antimony (Sb) 1.4E0 lb/TBtu or 2.0E-2 lb/GWh
    Arsenic (As) 1.5E0 lb/TBtu or 2.0E-2 lb/GWh
    Beryllium (Be) 1.0E-1 lb/TBtu or 1.0E-3 lb/GWh
    Cadmium (Cd) 1.5E-1 lb/TBtu or 2.0E-3 lb/GWh
    Chromium (Cr) 2.9E0 lb/TBtu or 3.0E-2 lb/GWh
    Cobalt (Co) 1.2E0 lb/TBtu or 2.0E-2 lb/GWh
    Lead (Pb) 1.9E+2 lb/TBtu or 1.8E0 lb/GWh
    Manganese (Mn) 2.5E0 lb/TBtu or 3.0E-2 lb/GWh
    Nickel (Ni) 6.5E0 lb/TBtu or 7.0E-2 lb/GWh
    Selenium (Se) 2.2E+1 lb/TBtu or 3.0E-1 lb/GWh
    b. Hydrogen chloride (HCl) 5.0E-4 lb/MMBtu or 5.0E-3 lb/MWh For Method 26A, collect a minimum of 1 dscm per run; for Method 26, collect a minimum of 120 liters per run. For ASTM D6348-033 or Method320, sample for a minimum of 1 hour.
    c. Mercury (Hg) 2.5E0 lb/TBtu or 3.0E-2 lb/GWh LEE Testing for 30 days with a sampling period consistent with that given in section 5.2.1 of appendix A to this subpart per Method 30B run or Hg CEMS or sorbent trap monitoring system only.
4. Liquid oil-fired unit—continental (excluding limited-use liquid oil-fired subcategory units) a. Filterable particulate matter (PM) 3.0E-2 lb/MMBtu or 3.0E-1 lb/MWh2 Collect a minimum of 1 dscm per run.
    OR OR
    Total HAP metals 8.0E-4 lb/MMBtu or 8.0E-3 lb/MWh Collect a minimum of 1 dscm per run.
    OR OR
    Individual HAP metals: Collect a minimum of 1 dscm per run.
    Antimony (Sb) 1.3E+1 lb/TBtu or 2.0E-1 lb/GWh
    Arsenic (As) 2.8E0 lb/TBtu or 3.0E-2 lb/GWh
    Beryllium (Be) 2.0E-1 lb/TBtu or 2.0E-3 lb/GWh
    Cadmium (Cd) 3.0E-1 lb/TBtu or 2.0E-3 lb/GWh
    Chromium (Cr) 5.5E0 lb/TBtu or 6.0E-2 lb/GWh
    Cobalt (Co) 2.1E+1 lb/TBtu or 3.0E-1 lb/GWh
    Lead (Pb) 8.1E0 lb/TBtu or 8.0E-2 lb/GWh
    Manganese (Mn) 2.2E+1 lb/TBtu or 3.0E-1 lb/GWh
    Nickel (Ni) 1.1E+2 lb/TBtu or 1.1E0 lb/GWh
    Selenium (Se) 3.3E0 lb/TBtu or 4.0E-2 lb/GWh
    Mercury (Hg) 2.0E-1 lb/TBtu or 2.0E-3 lb/GWh For Method 30B sample volume determination (Section 8.2.4), the estimated Hg concentration should nominally be <12 the standard.
    b. Hydrogen chloride (HCl) 2.0E-3 lb/MMBtu or 1.0E-2 lb/MWh For Method 26A, collect a minimum of 1 dscm per run; for Method 26, collect a minimum of 120 liters per run. For ASTM D6348-033 or Method 320, sample for a minimum of 1 hour.
    c. Hydrogen fluoride (HF) 4.0E-4 lb/MMBtu or 4.0E-3 lb/MWh For Method 26A, collect a minimum of 1 dscm per run; for Method 26, collect a minimum of 120 liters per run. For ASTM D6348-033 or Method 320, sample for a minimum of 1 hour.
5. Liquid oil-fired unit—non-continental (excluding limited-use liquid oil-fired subcategory units) a. Filterable particulate matter (PM) 3.0E-2 lb/MMBtu or 3.0E-1 lb/MWh2 Collect a minimum of 1 dscm per run.
    OR OR
    Total HAP metals 6.0E-4 lb/MMBtu or 7.0E-3 lb/MWh Collect a minimum of 1 dscm per run.
    OR OR
    Individual HAP metals: Collect a minimum of 2 dscm per run.
    Antimony (Sb) 2.2E0 lb/TBtu or 2.0E-2 lb/GWh
    Arsenic (As) 4.3E0 lb/TBtu or 8.0E-2 lb/GWh
    Beryllium (Be) 6.0E-1 lb/TBtu or 3.0E-3 lb/GWh
    Cadmium (Cd) 3.0E-1 lb/TBtu or 3.0E-3 lb/GWh
    Chromium (Cr) 3.1E+1 lb/TBtu or 3.0E-1 lb/GWh
    Cobalt (Co) 1.1E+2 lb/TBtu or 1.4E0 lb/GWh
    Lead (Pb) 4.9E0 lb/TBtu or 8.0E-2 lb/GWh
    Manganese (Mn) 2.0E+1 lb/TBtu or 3.0E-1 lb/GWh
    Nickel (Ni) 4.7E+2 lb/TBtu or 4.1E0 lb/GWh
    Selenium (Se) 9.8E0 lb/TBtu or 2.0E-1 lb/GWh
    Mercury (Hg) 4.0E-2 lb/TBtu or 4.0E-4 lb/GWh For Method 30B sample volume determination (Section 8.2.4), the estimated Hg concentration should nominally be <12 the standard.
    b. Hydrogen chloride (HCl) 2.0E-4 lb/MMBtu or 2.0E-3 lb/MWh For Method 26A, collect a minimum of 1 dscm per run; for Method 26, collect a minimum of 120 liters per run. For ASTM D6348-033 or Method 320, sample for a minimum of 2 hours.
    c. Hydrogen fluoride (HF) 6.0E-5 lb/MMBtu or 5.0E-4 lb/MWh For Method 26A, collect a minimum of 3 dscm per run. For ASTM D6348-033 or Method 320, sample for a minimum of 2 hours.
6. Solid oil-derived fuel-fired unit a. Filterable particulate matter (PM) 8.0E-3 lb/MMBtu or 9.0E-2 lb/MWh2 Collect a minimum of 1 dscm per run.
    OR OR
    Total non-Hg HAP metals 4.0E-5 lb/MMBtu or 6.0E-1 lb/GWh Collect a minimum of 1 dscm per run.
    OR OR
    Individual HAP metals: Collect a minimum of 3 dscm per run.
    Antimony (Sb) 8.0E-1 lb/TBtu or 7.0E-3 lb/GWh
    Arsenic (As) 3.0E-1 lb/TBtu or 5.0E-3 lb/GWh
    Beryllium (Be) 6.0E-2 lb/TBtu or 5.0E-4 lb/GWh
    Cadmium (Cd) 3.0E-1 lb/TBtu or 4.0E-3 lb/GWh
    Chromium (Cr) 8.0E-1 lb/TBtu or 2.0E-2 lb/GWh
    Cobalt (Co) 1.1E0 lb/TBtu or 2.0E-2 lb/GWh
    Lead (Pb) 8.0E-1 lb/TBtu or 2.0E-2 lb/GWh
    Manganese (Mn) 2.3E0 lb/TBtu or 4.0E-2 lb/GWh
    Nickel (Ni) 9.0E0 lb/TBtu or 2.0E-1 lb/GWh
    Selenium (Se) 1.2E0 lb/Tbtu or 2.0E-2 lb/GWh
    b. Hydrogen chloride (HCl) 5.0E-3 lb/MMBtu or 8.0E-2 lb/MWh For Method 26A, collect a minimum of 0.75 dscm per run; for Method 26, collect a minimum of 120 liters per run. For ASTM D6348-033 or Method 320, sample for a minimum of 1 hour.
    OR
    Sulfur dioxide (SO2)4 3.0E-1 lb/MMBtu or 2.0E0 lb/MWh SO2 CEMS.
    c. Mercury (Hg) 2.0E-1 lb/TBtu or 2.0E-3 lb/GWh LEE Testing for 30 days with a sampling period consistent with that given in section 5.2.1 of appendix A to this subpart per Method 30B run or Hg CEMS or sorbent trap monitoring system only.
7. Eastern Bituminous Coal Refuse (EBCR)-fired unit a. Filterable particulate matter (PM) 3.0E-2 lb/MMBtu or 3.0E-1 lb/MWh2 Collect a minimum of 1 dscm per run.
    OR OR
    Total non-Hg HAP metals 5.0E-5 lb/MMBtu or 5.0E-1 lb/GWh Collect a minimum of 1 dscm per run.
    OR OR
    Individual HAP metals: Collect a minimum of 3 dscm per run.
    Antimony (Sb) 8.0E-1 lb/TBtu or 8.0E-3 lb/GWh
    Arsenic (As) 1.1E0 lb/TBtu or 2.0E-2 lb/GWh
    Beryllium (Be) 2.0E-1 lb/TBtu or 2.0E-3 lb/GWh
    Cadmium (Cd) 3.0E-1 lb/TBtu or 3.0E-3 lb/GWh
    Chromium (Cr) 2.8E0 lb/TBtu or 3.0E-2 lb/GWh
    Cobalt (Co) 8.0E-1 lb/TBtu or 8.0E-3 lb/GWh
    Lead (Pb) 1.2E0 lb/TBtu or 2.0E-2 lb/GWh
    Manganese (Mn) 4.0E0 lb/TBtu or 5.0E-2 lb/GWh
    Nickel (Ni) 3.5E0 lb/TBtu or 4.0E-2 lb/GWh
    Selenium (Se) 5.0E0 lb/TBtu or 6.0E-2 lb/GWh
    b. Hydrogen chloride (HCl) 4.0E-2 lb/MMBtu or
4.0E-1 lb/MWh
For Method 26A at appendix A-8 to part 60 of this chapter, collect a minimum of 0.75 dscm per run; for Method 26, collect a minimum of 120 liters per run. For ASTM D6348-033 or Method 320 at appendix A to part 63 of this chapter, sample for a minimum of 1 hour.
    OR
    Sulfur dioxide (SO2)4 6E-1 lb/MMBtu or 9E0 lb/MWh SO2 CEMS.
    c. Mercury (Hg) 1.2E0 lb/TBtu or 1.3E-2 lb/GWh LEE Testing for 30 days with a sampling period consistent with that given in section 5.2.1 of appendix A to this subpart per Method 30B at appendix A-8 to part 60 of this chapter run or Hg CEMS or sorbent trap monitoring system only.
    OR
    1.0E0 lb/TBtu or 1.1E-2 lb/GWh LEE Testing for 90 days with a sampling period consistent with that given in section 5.2.1 of appendix A to this subpart per Method 30B run or Hg CEMS or sorbent trap monitoring system only.

1For LEE emissions testing for total PM, total HAP metals, individual HAP metals, HCl, and HF, the required minimum sampling volume must be increased nominally by a factor of 2.

2Gross output.

3Incorporated by reference, see §63.14.

4You may not use the alternate SO2 limit if your EGU does not have some form of FGD system and SO2 CEMS installed.

[85 FR 20850, Apr. 15, 2020]