Pollutant Units
(7 percent oxygen, dry basis)
HMIWI Emissions limits Averaging time1 Method for demonstrating compliance2
Particulate matter mg/dscm (gr/dscf) 87 (0.038) 3-run average (1-hour minimum sample time per run) EPA Reference Method 5 of appendix A-3 of part 60, or EPA Reference Method 26A or 29 of appendix A-8 of part 60.
Carbon monoxide ppmv 20 3-run average (1-hour minimum sample time per run) EPA Reference Method 10 or 10B of appendix A-4 of part 60.
Dioxins/furans ng/dscm total dioxins/furans (gr/109 dscf) or ng/dscm TEQ (gr/109 dscf) 240 (100) or 5.1 (2.2) 3-run average (4-hour minimum sample time per run) EPA Reference Method 23 of appendix A-7 of part 60.
Hydrogen chloride ppmv 810 3-run average (1-hour minimum sample time per run) EPA Reference Method 26 or 26A of appendix A-8 of part 60.
Sulfur dioxide ppmv 55 3-run average (1-hour minimum sample time per run) EPA Reference Method 6 or 6C of appendix A-4 of part 60.
Nitrogen oxides ppmv 130 3-run average (1-hour minimum sample time per run) EPA Reference Method 7 or 7E of appendix A-4 of part 60.
Lead mg/dscm (gr/103 dscf) 0.50 (0.22) 3-run average (1-hour minimum sample time per run) EPA Reference Method 29 of appendix A-8 of part 60.
Cadmium mg/dscm (gr/103 dscf) 0.11 (0.048) 3-run average (1-hour minimum sample time per run) EPA Reference Method 29 of appendix A-8 of part 60.
Mercury mg/dscm (gr/103 dscf) 0.0051 (0.0022) 3-run average (1-hour minimum sample time per run) EPA Reference Method 29 of appendix A-8 of part 60.

1Except as allowed under §60.56c(c) for HMIWI equipped with CEMS.

2Does not include CEMS and approved alternative non-EPA test methods allowed under §60.56c(b).

[74 FR 51407, Oct. 6, 2009]