[As stated in §60.4210(g), manufacturers of fire pump engines may use the following test cycle for testing fire pump engines:]

Open Table
Mode No. Engine speed1 Torque
(percent)2
Weighting
factors
1 Rated 100 0.30
2 Rated 75 0.50
3 Rated 50 0.20

1Engine speed: ±2 percent of point.

2Torque: NFPA certified nameplate HP for 100 percent point. All points should be ±2 percent of engine percent load value.