(a) Each vessel that carries combustible liquid cargo with a closed-cup flashpoint of 60 degrees C (140 degrees F) or higher must have:
(1) Only intrinsically safe electric systems in cargo tanks; and
(2) No storage battery in any cargo handling room.
(b) If a submerged cargo pump motor is in a cargo tank, it must meet the requirements of §111.105-31(d).
(c) Where the cargo is heated to within 15 °C of its flashpoint, the cargo pumproom must meet the requirements of §111.105-31(f) and the weather locations must meet §111.105-31(l).