46 CFR § 111.51-3
Protection of vital equipment
April 15, 2021
(a) The coordination of overcurrent protective devices must be demonstrated for all potential plant configurations.
(b) Overcurrent protective devices must be installed so that:
(1) A short-circuit on a circuit that is not vital to the propulsion, control, or safety of the vessel does not trip equipment that is vital; and
(2) A short-circuit on a circuit that is vital to the propulsion, control, or safety of the vessel is cleared only by the protective device that is closest to the point of the short-circuit.
[CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by CGD 94-108, 62 FR 23908, May 1, 1997]