(a) Each sailing school vessel must be equipped with fire pumps as required in Table 169.559(a).
Table 169.559(a)—Fire Pumps
Length | Exposed and partially protected water service | Protected water service |
---|---|---|
65 feet but less than 90 feet | 11 | 0 |
90 feet but less than 120 feet | 21 | 11 |
120 feet or greater | 32 | 11 |
1May be driven off a propulsion engine and may be used as a bilge pump.
2Must be driven by a source of power independent of the propulsion engine and may be used as a bilge pump.
3One pump may be driven off a propulsion unit and one pump may be used as a bilge pump. Pumps must be located in separate spaces.
(b) Fire pump capacity must be in accordance with the following:
Vessel length | Minimum capacity |
---|---|
Less than 90 ft | 5.5 m3/hr (25 gpm). |
90 feet but less than 120 ft | 11.0 m3/hr (50 gpm). |
Greater than 120 ft | 14.3 m3/hr (66.6 gpm). |
(c) Each fire pump must be fitted with a pressure gage on the discharge side of the pump.
(d) Each vessel must have a hand operated portable fire pump having a capacity of at least 1.1 m3/hr (5 gpm). This pump must be equipped with suction and discharge hose suitable for use in firefighting.