49 CFR § 236.589
Relays
November 18, 2020
(a) Each relay shall be removed from service, subjected to thorough test, necessary repairs and adjustments made, and shall not be replaced in service unless its operating characteristics are in accordance with the limits within which such relay is designed to operate, as follows:
(1) Master or primary relays of torque type depending on spring tension to return contacts to deenergized position in noncoded continuous inductive automatic train stop or train control system, at least once every two years; and
(2) All other relays, at least once every six years.
(b) [Reserved]
[49 FR 3387, Jan. 26, 1984]