- (a)Each fuel tank must not be integral with any boat structure or mounted on an engine.
- (b)Each fuel tank must not move at the mounting surface more than onefourth inch in any direction.
- (c)Each fuel tank must not support a deck, bulkhead, or other structural component.
- (d)Water must drain from the top surface of each metallic fuel tank when the boat is in its static floating position.
- (e)Each fuel tank support, chock, or strap that is not integral with a metallic fuel tank must be insulated from the tank surface by a nonmoisture absorbing material.
- (f)Cellular plastic must not be the sole support for a metallic fuel tank.
- (g)If cellular plastic is the sole support of a non-metallic fuel tank, the cellular plastic must meet the requirements of § 183.516 (b) or (c).
- (h)Each fuel tank labeled under § 183.514(b)(8) for installation aft of the boat's half length must be installed with its center of gravity aft of the boat's half length.