40 CFR §60.4372a
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
- (a)If you elect to demonstrate compliance with a SO2 emissions standard according to § 60.4333a(d)(3), you must maintain on-site records (such as a current, valid purchase contract, tariff sheet, or transportation contract) documenting that total sulfur content for the fuel combusted in your stationary combustion turbine at all times does not exceed the conditions specified in paragraph (b) through (e) of this section, as applicable to your stationary combustion turbine.
- (b)If your stationary combustion turbine is subject to the SO2 emissions standard in § 60.4330a(a), then the fuel combusted must have a potential SO2 emissions rate of 26 ng/J (0.060 lb/MMBtu) heat input or less.
- (c)If your stationary combustion turbine is subject to the SO2 emissions standard in § 60.4330a(b), then the total sulfur content of the gaseous fuel combusted must be 650 (mg/scm) (28 gr/100 scf).
- (d)If your stationary combustion turbine is subject to the SO2 emissions standard in § 60.4330a(c) or (d), the total sulfur content of the fuel combusted must be:
- (e)Representative fuel sampling data following the procedures specified in section 2.3.1.4 or 2.3.2.4 in appendix D to part 75 of this chapter documenting that the fuel meets the part 75 requirements to be considered either pipeline natural gas or natural gas. Your stationary combustion turbine may not cause to be discharged into the atmosphere any gases that contain SO2 in excess of: