40 CFR §60.4405
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
If you elect to install and certify a NOX-diluent CEMS under § 60.4345, then the initial performance test required under § 60.8 may be performed in the following alternative manner:
- (a)Perform a minimum of nine RATA reference method runs, with a minimum time per run of 21 minutes, at a single load level, within plus or minus 25 percent of 100 percent of peak load, while the source is combusting the fuel that is a normal primary fuel for that source. The ambient temperature must be greater than 0 °F during the RATA runs.
- (b)For each RATA run, concurrently measure the heat input to the unit using a fuel flow meter (or flow meters) and measure the electrical and thermal output from the unit.
- (c)Use the test data both to demonstrate compliance with the applicable NOX emission limit under § 60.4320 and to provide the required reference method data for the RATA of the CEMS described under § 60.4335.
- (d)Compliance with the applicable emission limit in § 60.4320 is achieved if the arithmetic average of all of the NOX emission rates for the RATA runs, expressed in units of ppm or lb/MWh, does not exceed the emission limit.