StacksVerified U.S. regulatory reference

40 CFR Part 62, Table 3

Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov
Operatingparametersto bemonitoredMinimum frequencyHMIWI
Data measurementData recordingHMIWI with combustion control only | HMIWI with dry scrubber followed by FF | HMIWI with wet scrubber | HMIWI with dry scrubber followed by FF and wet scrubber | HMIWI with SNCR system
Maximum operating parameters: | | | | |
Maximum charge rateOnce per chargeOnce per charge | ✓ | ✓ | ✓ | ✓ | ✓
Maximum FF inlet temperatureContinuousOnce per minute | | ✓ | | ✓ |
Maximum flue gas temperatureContinuousOnce per minute | | | ✓ | ✓ |
Minimum operating parameters: | | | | |
Minimum secondary chamber temperatureContinuousOnce per minute | ✓ | ✓ | ✓ | ✓ | ✓
Minimum dioxin/furan sorbent flow rateHourlyOnce per hour | | ✓ | | ✓ |
Minimum HCl sorbent flow rateHourlyOnce per hour | | ✓ | | ✓ |
Minimum mercury (Hg) sorbent flow rateHourlyOnce per hour | | ✓ | | ✓ |
Minimum pressure drop across the wet scrubber or minimum horsepower or amperage to wet scrubberContinuousOnce per minute | | | ✓ | ✓ |
Minimum scrubber liquor flow rateContinuousOnce per minute | | | ✓ | ✓ |
Minimum scrubber liquor pHContinuousOnce per minute | | | ✓ | ✓ |
Minimum reagent flow rateHourlyOnce per hour | | | | | ✓

[78 FR 28076, May 13, 2013]