46 CFR §108.171
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
The following are Class I, Division 1 locations:
- (a)An enclosed space that contains any part of the mud circulating system that has an opening into the space and is between the well and final degassing discharge.
- (b)An enclosed or semi-enclosed location that is below the drill floor, and contains a possible source of gas release.
- (c)An enclosed space that is on the drill floor, and is not separated by a solid, gas-light floor from the spaces specified in paragraph (b) of this section.
- (d)A space that would normally be considered a Division 2 location under § 108.173 but where combustible or flammable gases might accumulate.
- (e)A location in the weather, or a semi-enclosed location, except as provided in paragraph (b) of this section that is within 1.5 m (5 ft.) of the boundary of any—
- (f)Except as provided in § 108.175, an enclosed space that has an opening into a Class I, Division 1 location.