- (a)The ventilation system for each enclosed classified location must be designed to maintain a pressure differential between the enclosed classified location and each non-classified location adjacent to the enclosed classified location, so as to prevent the discharge of ignitable gases into the non-classified adjacent locations.
- (b)Each air intake must be outside of enclosed classified locations.
- (c)Each unit must have alarms that are powered independently of the ventilation motor power and control circuitry and sound at a continuously manned station when—
- (d)Each ventilation system for enclosed classified locations must provide a complete change of air every five minutes.