- (a)Mechanical ventilation for spaces protected by a CO2 system must be designed to shut down automatically when the system is activated.
- (b)Each space that is protected by a CO2 system and that has natural ventilation must have a means for closing that ventilation.
- (c)Each space protected by a CO2 system must have the following means for closing the openings to the space from outside the space: