StacksVerified U.S. regulatory reference

46 CFR §111.12-9

Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov
  1. (a)The current-carrying capacity of generator cables must not be:
    1. (1)Less than 115 percent of the continuous generator rating; or
    2. (2)Less than 115 percent of the overload for a machine with a 2 hour or greater overload rating.