46 CFR §111.12-9
- (a)The current-carrying capacity of generator cables must not be:
- (1)Less than 115 percent of the continuous generator rating; or
- (2)Less than 115 percent of the overload for a machine with a 2 hour or greater overload rating.
- (b)Generator cables must not be in the bilges.