46 CFR §111.30-17
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
- (a)Each circuit that supplies a device on a switchboard, except a circuit under paragraph (b) of this section, must have overcurrent protection.
- (b)A circuit that supplies a device on a switchboard must not have overload protection if it supplies:
- (c)If short circuit protection is used in any of the circuits listed in paragraph (b) of this section, it must be set at not less than 500% of the expected current.
- (d)A secondary circuit of a current transformer must not be fused, and the circuit from a current transformer to a device that is not in the switchboard must have a high voltage protector to short the transformer during an open circuit.