46 CFR §111.30-19

Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov
  1. (a)General. Each bus must meet the requirements of either—
    1. (1)Section 5.10 of IEEE 45.7-2012 (incorporated by reference; see § 110.10-1 of this subchapter); or
    2. (2)IEC 60092-302:1997 (clause 7) (incorporated by reference; see § 110.10-1 of this subchapter).
  2. (b)Wiring. Instrumentation and control wiring must be—
    1. (1)Suitable for installation within in a switchboard enclosure and be rated at 90 °C or higher;
    2. (2)Stranded copper;
    3. (3)No. 14 AWG (2.10 mm 2) or larger or must be ribbon cable or similar conductor size cable recommended for use in low-power instrumentation, monitoring, or control circuits by the equipment manufacturer;
    4. (4)Flame-retardant meeting test VW-1 of ANSI/UL 2556 or IEC 60332-1-1:2015 and IEC 60332-1-2:2015 (all incorporated by reference; see § 110.10-1 of this subchapter); and
    5. (5)Extra flexible, if used on a hinged panel.