46 CFR §111.50-5
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
- (a)Location in circuit. Overcurrent devices must be at the point where the conductor to be protected receives its supply, except as follows:
- (1)The generator overcurrent protective device must be on the ship's service generator switchboard. (See § 111.12-11(g) for additional requirements.)
- (2)The overcurrent protection for the shore connection conductors must meet § 111.30-25(f).
- (3)If the overcurrent device that protects the larger conductors also protects the smaller conductors, an overcurrent device is not required at the supply to the smaller conductors.
- (4)If the overcurrent device protecting the primary side of a transformer also protects the conductors connected to the secondary side, as determined by multiplying the current-carrying capacity of the secondary conductor by the secondary to primary transformer voltage ratio, and this protection meets § 111.20-15 of this chapter, an overcurrent device is not required at the supply to the secondary side conductors.
- (b)Location on vessel. Each overcurrent device: