46 CFR §111.79-1
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
- (a)There must be a sufficient number of receptacle outlets in the crew accommodations for an adequate level of habitability.
- (b)There must be a sufficient number of receptacle outlets throughout the machinery space so that any location can be reached by a portable power cord having a length not greater than 24 meters (75 feet).
- (c)Each receptacle outlet must be compatible with the voltage and current of the circuit in which it is installed.
- (d)Each receptacle outlet must be suitable for the environment in which it is installed and constructed to the appropriate NEMA or IEC protection standard as referenced in § 111.01-9. Special attention must be given to outlets in hazardous locations.
- (e)A receptacle outlet must not have any exposed live parts with the plug opening uncovered.