46 CFR §111.97-7

Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov
  1. (a)Each distribution panelboard for a watertight door system must be above the uppermost continuous deck and must have means for locking.
  2. (b)Each feeder supplying a watertight door operating system must be above the uppermost continuous deck.
  3. (c)Each watertight door operating system must have a separate branch circuit.