46 CFR §112.50-1
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
- (a)The prime mover of a generator set must have:
- (b)The fuel used must have a flashpoint of not less than 110 degrees F (43 degrees C).
- (c)The room that has the generator set must have intake and exhaust ducts to supply adequate cooling air.
- (d)The generator set must be capable of carrying its full rated load within 45 seconds after cranking is started with the intake air, room ambient temperature, and starting equipment at O°C. The generator's prime mover must not have a starting aid to meet this requirement, except that a thermostatically-controlled electric water-jacket heater connected to the final emergency bus is permitted.
- (e)The generator set must start by hydraulic, compressed air, or electrical means.
- (f)The generator set must maintain proper lubrication when inclined to the angles specified in § 112.05-5(c), and must be arranged so that it does not spill oil under a vessel roll of 30 degrees to each side of the vertical.
- (g)The following automatic shutdowns are required for the generator set:
- (h)The following audible alarms are required for the generator set if the prime mover is a diesel engine:
- (j)An independent fuel supply must be provided for the prime mover.
- (k)Each emergency generator that is arranged to be automatically started must be equipped with a starting device with an energy-storage capability of at least six consecutive starts. A second, separate source of starting energy may provide three of the required six starts. If a second source is provided, the system need only provide three consecutive starts.