46 CFR §112.50-5

Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov
An electric starting system must have a starting battery with sufficient capacity for at least six consecutive starts. A second, separate source of starting energy may provide three of the required six starts. If a second source is provided, the electrical starting system need only provide three consecutive starts.