46 CFR §113.25-16
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
- (a)Each fuse in a general emergency alarm system must meet the requirements of part 111, subpart 111.53, of this chapter.
- (b)Each overcurrent protection device must cause as wide a differential as possible between the rating of the branch circuit overcurrent protection device and that of the feeder overcurrent protection device.
- (c)The capacity of the feeder overcurrent device must be as near practicable to 200 percent of the load supplied. The capacity of a branch circuit overcurrent device must not be higher than 50 percent of the capacity of the feeder overcurrent device.