46 CFR §118.420

Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov
  1. (a)A pre-engineered fixed gas fire extinguishing system must:
    1. (1)Be approved by the Commandant;
    2. (2)Be capable of manual actuation from outside the space in addition to automatic actuation by a heat detector;
    3. (3)Automatically shut down all power ventilation systems and all engines that draw intake air from within the protection space; and
    4. (4)Be installed in accordance with manufacturer's instructions.
  2. (b)A vessel on which a pre-engineered fixed gas fire extinguishing system is installed must have the following equipment at the operating station:
    1. (1)A light to indicate discharge;
    2. (2)An audible alarm that sounds upon discharge; and
    3. (3)A means to reset devices used to automatically shut down ventilation systems and engines as required by paragraph (a)(3) of this section.
  3. (c)Only one pre-engineered fixed gas fire extinguishing system is allowed to be installed in each space protected by such a system.