46 CFR §129.323
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
If an OSV uses two or more generators to supply electricity for the ship's service loads, to comply with § 129.310(a) of this subpart, the following requirements must be met:
- (a)Each generator must have an independent prime mover.
- (b)The circuit breaker of a generator to be operated in parallel with another generator must comply with §§ 111.12-11(f), 111.30-19(a), and 111.30-25(d) of this chapter.
- (c)The circuit breaker of a generator not to be operated in parallel with another generator must be interlocked to prevent that generator from being connected to the switchboard simultaneously with another.