46 CFR §129.326

Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov
If a dual-voltage generator is installed on an OSV—
  1. (a)The neutral of the dual-voltage system must be solidly grounded at the switchboard's neutral bus and be accessible for checking the insulation resistance of the generator; and
  2. (b)Ground detection must be provided that—
    1. (1)For an alternating-current system, complies with § 111.05-27 of this chapter; and
    2. (2)For a direct-current system, complies with § 111.05-29 of this chapter.