46 CFR §129.420
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
On each vessel of 100 or more gross tons, each branch circuit for lighting must comply with § 111.75-5 of this chapter, except that—
- (a)Appliance loads, electric-heater loads, and isolated small-motor loads may be connected to a lighting-distribution panelboard; and
- (b)Branch circuits, other than for lighting, connected to the lighting-distribution panelboard permitted by paragraph (a) of this section may have fuses or circuit breakers rated at more than 30 amperes.