46 CFR §132.330

Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov
  1. (a)Each fire monitor of the fire main system must be fitted with a shut-off valve at the monitor and at the connection to the fire main discharge manifold required by § 132.120(h) of this part.
  2. (b)Fire monitor piping must comply with § 132.110 of this part.
  3. (c)Each fire monitor must be protected against over-pressure.