- (a)Each halocarbon cylinder forming part of a clean agent fixed fire extinguishing system must be:
- (1)Retested at least once every 12 years and before recharging if it has been discharged and more than five years have elapsed since the last test; or
- (2)As an alternative, a cylinder conforming to the requirements of 49 CFR 180.209(g) may be given the complete external visual inspection in lieu of hydrostatic testing provided for by that section.
- (b)A halocarbon cylinder must be removed from service if it:
- (c)Flexible connections between cylinders and discharge piping for halocarbon fire extinguishing systems must be renewed or retested in accordance with section 7.3 of NFPA 2001 (incorporated by reference, see § 147.7).