46 CFR §153.940
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
No person may mark a hose assembly as meeting the standards of this section unless the hose assembly meets the following requirements:
- (a)Each hose assembly must have:
- (b)Each hose assembly must be marked with the:
- (c)A cargo hose assembly must have a minimum bursting pressure as stated by the manufacturer of at least 5152 kPa gauge (approx. 750 psig).
- (d)The working pressure marked on a hose must meet the following:
- (e)A cargo hose assembly must be inspected and tested by placing it in a straight, horizontal position so that its entire external surface is accessible. It must be ascertained that the hose assembly:
- (1)Has no loose covers, kinks, bulges, soft spots, and no gouges, cuts, or slashes that penetrate any hose reinforcement;
- (2)Has no external and, to the extent internal inspection is possible with both ends of the hose open, no internal deterioration; and
- (3)Does not burst, bulge, leak, or abnormally distort under static liquid pressure at least as great as the recommended working pressure.