The person in charge of cargo transfer may not authorize cargo discharge by gas pressurization unless:
- (a)The tank to be offloaded has an SR or PV venting system;
- (b)The pressurization medium is either the cargo vapor or a nonflammable, nontoxic gas inert to the cargo; and
- (c)The pressurizing line has:
- (1)A pressure reducing valve whose setting does not exceed 90% of the tank's relief valve setting and a manual control valve between the pressure reducing valve and the tank; or
- (2)For an inert gas medium:
- (i)A safety relief valve with a cross sectional flow area at least equal to that of the pressurizing line and whose relieving pressure does not exceed 90 percent of the tank's relief valve setting;
- (ii)A manual control valve between the safety relief valve and the tank; and
- (iii)A check valve between the manual control valve and the tank.