  1. (a)Electrical equipment that is required to be intrinsically safe or explosion proof under § 154.1010 must be specially approved by the Commandant or listed as intrinsically safe or explosion proof by an independent laboratory that is specially approved by the Commandant (CG-OES), for Class I Division I locations and the Group that is specified in Table 4 for the cargo carried.
  2. (b)Each submerged cargo pump motor installation must be specially approved by the Commandant (CG-OES).
  3. (c)Electrical equipment that must be intrinsically safe to meet § 154.1010 must meet the definition in § 110.15-100(i) of this chapter.
  4. (d)Electrical equipment that must be explosion proof to meet § 154.1010 must meet § 110.15-65(e) of this chapter.