46 CFR §154.1125
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
- (a)Each pipe, fitting, and valve for each water spray system must meet Part 56 of this chapter.
- (b)Each water spray main that protects more than one area listed in § 154.1110 must have at least one isolation valve at each branch connection and at least one isolation valve downstream of each branch connection to isolate damaged sections.
- (c)Each valved cross-connection from the water spray system to the fire main must be outside of the cargo area.
- (d)Each pipe, fitting, and valve for the water spray system must be made of fire resistant and corrosion resistant materials, such as galvanized steel or galvanized iron pipe.
- (e)Each water spray system must have a means of drainage to prevent corrosion of the system and freezing of accumulated water in subfreezing temperatures.
- (f)Each water spray system must have a dirt strainer that is located at the water spray system manifold or pump.