46 CFR §154.1135
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
- (a)Water to the water spray system must be supplied by:
- (b)Operation of a water spray system must not interfere with simultaneous operation of the fire main system at its required capacity. There must be a valved cross-connection between the two systems.
- (c)Except as allowed under paragraph (d) of this section, each pump for each water spray system must have the capacity to simultaneously supply all areas named in § 154.1110.
- (d)If the water spray system is divided into sections, the pump under paragraph (a) of this section must have the capacity to simultaneously supply the required discharge density under § 154.1115(a) for:
- (1)The areas in §§ 154.1110(f) through (h) and 154.1115(b); and
- (2)The largest section that includes the required protection under § 154.1110 (a), (b), and (c).