- (a)A vessel with a cargo carrying capacity less that 1000 m 3 (35,300 ft. 3) must have at least one self-contained dry chemical storage unit for the cargo area with an independent inert gas pressurizing source adjacent to each unit.
- (b)A vessel with a cargo carrying capacity of 1000 m 3 (35,300 ft. 3) or more must have at least two self-contained dry chemical storage units for the cargo area with an independent inert gas pressurizing source adjacent to each unit.
- (c)A vessel with bow and stern loading and discharge areas must have at least one self-contained dry chemical storage unit with an independent inert gas pressurizing source adjacent to the unit for each area.
- (d)Each dry chemical storage unit and associated piping must be designed for:
- (e)Each fully charged dry chemical storage unit must have the greater of the following: